0.6/1 kV PVC Insulated Low Voltage Power Cables
Application
Used as energy network, illumination and installation cables for indoor and outdoor where there is no mechanical stress. Can be used underground; laid in conduits and in industrial plants.
Construction
1.Conductor: Fine-Flexible copper
2.Insulation: PVC
3.Filler: Special Filler
4.Outer Sheath: PVC
Max. Operating Temperature: 70° C
Industrial Use
Min. Bending Radius: 15 x D
Marking - PROTON CABLE 3x16+10 mm² 0.6/1 kV
NYY FLEX
Part Number | Nominal Cross Section mm² | Overall Diameter mm approx. | Conductor DC Resistance at 20° C max. ohm/km |
---|---|---|---|
PC600 | 2 x 6 | 13.7 | 3.30 |
PC602 | 2 x 10 |
16.4 | 1.91 |
PC604 |
2 x 16 | 19.4 | 1.21 |
PC606 |
2 x 25 | 23.7 | 0.782 |
PC608 |
2 x 35 | 25.7 | 0.554 |
PC610 |
2 x 50 | 30.1 | 0.386 |
PC612 | 3 x 6 | 14.4 | 3.30 |
PC614 | 3 x 10 | 17.4 | 1.91 |
PC616 | 3 x 16 | 20.5 | 1.21 |
PC618 | 3 x 25 | 25.1 | 0.780 |
PC620 | 3 x 35 | 27.3 | 0.554 |
PC622 | 3 x 50 | 32.0 | 0.386 |
PC624 | 3 x 16 + 10 | 21.6 | 1.21/1.91 |
PC626 | 3 x 25 + 16 | 26.2 | 0.780/1.21 |
PC628 | 3 x 35 + 16 | 28.0 | 0.554/1.21 |
PC630 | 3 x 50 +25 | 34.5 | 0.386/0.780 |