0.6/1 kV PVC Insulated Low Voltage Power Cables
Application
Used as energy network, illumination and installation cables for indoor and outdoor where there is no mechanical stress. Can be used underground; laid in conduits and in industrial plants.
Construction
1.Conductor: Solid or stranded copper
2.Insulation: PVC
3.Outer Sheath: PVC
Max. Operating Temperature: 70° C
Industrial Use
Min. Bending Radius: 15 x D
Marking - PROTON CABLE 3x25+16 mm² 0.6/1 kV
NYY
Part Number | Nominal Cross Section mm² | Overall Diameter mm approx. | Conductor DC Resistance at 20° C max. ohm/km | Current Carrying Capacity in Ground (A) | Current Carrying Capacity in Air (A) |
---|---|---|---|---|---|
PC500 | 1 x 4 | 8 | 4.61 | - | 37 |
PC502 | 1 x 6 | 8.5 | 3.08 | - | 48 |
PC504 | 1 x 10 | 9.2 | 1.83 | - | 66 |
PC506 | 1 x 16 | 10.2 | 1.15 | 107 | 89 |
PC508 | 1 x 25 | 11.6 | 0.727 | 137 | 118 |
PC510 | 1 x 35 | 13 | 0.524 | 165 | 145 |
PC512 | 1 x 50 | 14.4 | 0.387 | 195 | 176 |
PC514 | 1 x 70 | 16 | 0.268 | 239 | 224 |
PC516 | 1 x 95 | 18 | 0.193 | 287 | 271 |
PC518 | 1 x 1.5 | 10.5 | 12.1 | 32 | 20 |
PC520 | 1 x 2.5 | 11.5 | 7.41 | 42 | 27 |
PC522 | 1 x 4 | 13 | 4.61 | 54 | 37 |
PC524 | 1 x 6 | 15 | 3.08 | 68 | 48 |
PC526 | 1 x 10 | 16 | 1.83 | 90 | 66 |
PC528 | 1 x 16 | 18 | 1.15 | 116 | 89 |
PC530 | 1 x 25 | 22 | 0.727 | 150 | 118 |
PC532 | 1 x 35 | 24 | 0.524 | 181 | 145 |
PC534 | 1 x 50 | 27 | 0.387 | 215 | 176 |